Warranty
36-Month Return to Base Warranty
Features
- Top-level on-line double conversion UPS for mission-critical applications
- Unity output power factor
- LCD multi-language color display (gravity sensing)
- On-line (VFI) mode efficiency up to 94% at full load
- Active ECO mode efficiency up to 98%
- Energy Star® 2.0 certified
- Controllable and programmable output sockets
- Integrated solution with batteries and electronics
- External battery cabinet's auto-detection
- Operates at full power up to 40ºC (up to 50ºC with derating) Intelligent Communication ready
- Safety Agency Approved Category B IEC 61000-4-5 Surges/Lightning protection capability)
Specifications
Rating | 750VA/750W | |
Input | Rated Voltage | 230VAC |
Rated Frequency | 50/60Hz | |
Frequency Range | 40 to 70 Hz | |
Power Factor | ≥0.99 | |
Output | Nominal Voltage | 200/208/220/230/240 VAC |
Waveform | Sine wave | |
Inverter Overload Capability | >200% minimum 250 mS, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds; 105 to 125% for 60 seconds |
|
Efficiency in Online Mode | Up to 94% | |
Inverter Bypass | Up to 98% | |
Output Receptacles | 6x EN60320/C13 1x EN60320/C19 |
|
Internal Battery | Rated Voltage | 72Vdc |
Charger Current | Nominal 2.2 A; Maximum 8A | |
Type | Valve-regulated, non-spillable, lead acid | |
Quantity x V x Rating | 6 x 12V x 9.0Ah | |
End Cell Voltage | 1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc, can be selected by PARAMSET) |
|
Floating Voltage | Equalize charge: 2.35 V/cell; Float charge: 2.27 V/cell | |
Battery Voltage Range | 60 Vdc to 84.6 Vdc | |
Internal Battery Backup Time (Approximate) |
10% Load Capacity: 70 mins 20% Load Capacity: 31.5 mins 30% Load Capacity: 18.5 mins 40% Load Capacity: 12.5 mins 50% Load Capacity: 9 mins 60% Load Capacity: 7 mins 70% Load Capacity: 6 mins 80% Load Capacity: 4.5 mins 90% Load Capacity: 4 mins 100% Load Capacity: 3 mins |
|
General | Operating Temperature, °C | Full power up to 40 ºC (up to 50 ºC with derating) |
Storage Temperature, °C | - 15 to + 40 | |
Relative Humidity | 0 to 95% non-condensing | |
Operating Elevation | Up to 3,000 m at 25°C without derating | |
Audible Noise | <46 dBA, at 1 meter from sides, <43 dBA, at 1 meter from rear |
|
Safety | IEC62040-1:2008 version, GS mark; CE: UL1778 5th Edition and CSA 22.2 No 107.1 |
|
EMI/EMC/C-Tick EMC | EN 62040-2:2006; EN 61000-3-3:2013; EN 61000-3-3:2013 |
|
Transportation | ISTA Procedure 1 A | |
Surge Immunity | ANSI C62.41 Category B IEC 61000-4-5 Surges/Lighting | |
Dimensions (mm) | 540 (w) x 430 (d) x 85 (h) | |
Weight | 28.5kg |